♦ High Power Test Laboratories
♦ Motor Starting
♦ Electric Arc Furnaces
♦ Induction Furnaces
♦ Stainless steel grid elements
♦ Typically 2 mm hot-dip galvanized steel enclosure on demand
♦ High thermal capacity to absorb high currents
♦ Rugged-shock resistant construction
♦ High Altitude ratings
♦ Corrosion-resistant nameplate
♦ Specially designed units for hazardous and extreme locations
♦ Designed and tested to applicable IEC and IEEE standards
Approximate phase to earth fault current in 240-5000 V networks:
High Resistance Grounding (HGR) systems are used in power systems where phase to ground short-circuit current is desired to be limited zero to a few amperes by placing high resistance between the neutral point of the transformer (or generator) and ground. As it is not possible to locate the fault point in delta-connected systems, an artificial neutral point is created and delta connected system can be grounded. This allows a fault current of a few amperes thus locating the fault point gets easy. When the neutral point is grounded thru high resistance, both continuity of operation is provided during a fault condition and sufficient current (typically between 2A and 10A) flow is provided for ease of locating the fault point.
♦ 0 – 10A analog ammeter and 0 – 250V analog voltmeter with setting on panel
♦ Automatic door switch for power shut down
♦ Test button to indicate fault
♦ Green light for normal conditions
♦ Intermittent alarm and red light during ground fault
♦ Pulse/Normal Selector swith to magnify current and intermittent pulse during ground fault.
♦ Auxilliary free contacts at pulse and alarm position during fault
♦ Dimensions (LxWxH)= 60 x 100 x 200 cm (Other enclosure types avaible on demand.)
♦ Suitable for 240….4160V three phase systems
♦ 0 – 10A analog ammeter and 0 – 250V analog voltmeter with setting on panel
♦ Automatic door switch for power shut down
♦ Test button to indicate fault
♦ Green light for normal conditions
♦ Intermittent alarm and red light during ground fault
♦ Pulse/Normal Selector swith to magnify current and intermittent pulse during ground fault.
♦ Auxilliary free contacts at pulse and alarm position during fault
♦ Dimensions (LxWxH)= 60 x 100 x 200 cm (Other enclosure types avaible on demand.)
♦ Suitable for 240….4160V three phase systems
Dynamic braking resistors are used to stop ac and dc motors with inverter control. Design of Dynamic Braking Resistors depends on recommended braking periods or specific applications.
Electric motors in certain cases run as a generator by the machine that is operating and feeds the electric network. If the motor is required to stop or slow down to nominal speed in such cases, a resistor with suitable ohmic and watt ratings is connected to inverter braking terminals to convert the energy generated by the motor to DC and convert it into heat through dynamic braking resistor. The required power of a braking resistor (dynamic braking) to brake a motor that rotates at maximum speed and maximum load must be equal to the power of the motor. However, as the braking time is generally around a few seconds, a resistor power rating that is smaller than the motor’s rated power can be overloaded for a short time to provide an economical way of braking.
Warning 1
Ohmic value of resistors for braking purposes can not be less than stated dynamic braking resistor manufacturer catalog values. Otherwise, the inverter and resistor can be damaged. If the ohmic value chosen is larger than the inverter catalog’s recommended value, braking time gets longer. Braking time is determined by the weight and speed of rotating parts.
Warning 2
If braking time is unknown, as a safety tolerance, the resistor watt rating should be chosen the same as the motor’s power rating.
Example 1
Suppose that an electric motor with a power rating of 100 kW, is lifting a load for 60 seconds and descending the load for 60 seconds with dynamic braking. The operation factor (ED%) for this system will be ED% = 60/(60+60) = 50 % . As a result of this fact, this braking resistor will operate for 60 seconds and cool down for 60 seconds within the operating cycle of 120 seconds of the crane. As a result of this fact, a braking resistor that will brake a 100 kW motor for 60 seconds must withstand operating 0,50 x 100 = 50 kW continuously and 100 kW for 60 seconds.
Example 2
If a 100 kW electric motor is running 10 seconds and dynamic braking is being applied for 80 seconds within a time frame of 90 seconds, as the braking time is longer than 60 seconds, it is considered as continuous braking and a dynamic braking resistor which can withstand 100 kW continuously is strongly recommended.
Example 3
Suppose a 100 kW electric motor is rotating a fan and after the frequency of the motor becomes zero, the fan stops with a braking resistor at 6 seconds. If the motor will start running after Tr = 54 seconds, a smaller wattage rating for this application can be selected.
Overload time (Tbr) = 6 seconds.
Braking Resistor Power at Overload (Pbr) = Pmotor x Tbr / (Tbr + Tc) = 100 x 6 / (6+54) = 10 kW . So a resistor with a power rating of 10 kW is enough for his application.
Over Load Multiplier of this resistor (OLM) = (6+54)/6 = 10.
So a 10 kW resistor must withstand the power of 10 x 10 = 100 kW for 6 seconds.
The relationship between Over Load Multiplier / Cooling time / Over Load Time can be seen in the following graph.
Up to 13,8 kV 3000 A
♦ Test terminals for current and voltage transformers secondaries
♦ Designed and tested to applicable IEC and IEEE standards
♦ Stainless steel resistor elements
♦ Excellent high voltage strength
♦ Low inductance resistor elements for easy tuning
♦ A large variety of harmonic filters for the optimum solution
♦ Stainless steel, hot-dip galvanized steel, or aluminum resistor enclosures on demand
♦ Corrosion and heat resistant electrostatic paint for indoor and outdoor applications
♦ Insulators with high creepage distance are provided on demand for highly polluted areas and high altitudes
♦ Compact design
♦ Elevation stands are available
♦ Cooling fans are available on demand
♦ Overhead cranes
♦ Lift trucks
♦ Machine tools
♦ Conveyors
♦ Cement Plants
♦ Industrial Controls
♦ Steel Mills
♦ Ships and Submarines
♦ Designed and tested to applicable IEC and IEEE Standards
♦ Designed for all wound motor, squirrel cage motor, and induction motors
♦ Durable construction
♦ Stainless steel grid or resistance alloy elements
♦ High performance in heavily polluted areas
♦ AC Squirrel Cage Induction Motor Resistors
♦ Crane control resistors
♦ Starting Resistors
♦ Speed Control Resistors
♦ Application
♦ Power of motor
♦ Rotor current
♦ Rotor voltage
♦ Starting Torque
♦ Number of speeds
♦ Desired starting time (seconds)
♦ Duty Cycle
Neutral Grounding Resistors are used for resistance grounding of the industrial power systems. They are generally connected between ground and neutral transformers, generators, and grounding transformers. Neutral Grounding Resistors are used to limit maximum fault current to a value that will not damage the equipment in the power system, yet allow sufficient flow of fault current to operate protective relays to clear the fault. Although it is possible to limit fault currents with high resistance Neutral Grounding Resistors, phase to ground short circuit currents can be extremely reduced. As a result of this fact, protection devices may not sense the fault. Therefore, it is the most common application to limit single phase fault currents with low resistance Neutral Grounding Resistors.
♦ Stainless-steel resistor elements
♦ Current transformer included (EN 60044-1)
♦ Bolted resistor element connections instead of welded connections in order to be able to assemble spare parts on-site immediately
♦ Typically, RAL 7032(and others) painted
♦ Typically, 2 mm hot-dip galvanized steel enclosure
♦ High thermal capacity to absorb high currents
♦ High altitude ratings
♦ Custom made lifting eyes provide secure lifting
♦ Rugged shock-resistant construction
RC Filter components are made of low inductance resistors and capacitors in order to protect M.V. motors, generators and dry-type transformers, shunt reactors against very fast transient and overvoltages. R–C snubber filters are connected in parallel between motors, generators, etc., and switchgear.
♦ Longer insulation lifetime for machinery
♦ Protects against insulation failures between windings
♦ Protects against reignitions between the contacts of vacuum circuit breakers and other switchgear due to high-frequency overvoltage
♦ Protects against high-frequency overvoltage specifically caused by arc furnaces
♦ Optional earth fault relay by arc furnaces
Large motors, generators, induction and arc furnaces, shunt reactors, dry-type transformers.